Quantor MiniChilly

This page is made to support users in understanding the Eliwell EWPlus961 controller unit installed on the Quantor MiniChilly models sold by Brewtools.

Current models

7712969 – MiniChilly 03, 300W

7712970 – MiniChilly 09, 900W

7712971 – MiniChilly 17, 1.7kW

The controller ships with a default configuration based on the manufacturers best practice. Since the MiniChilly can be used with clean water as well as glycol mixture, it might be relevant to the user to change the lower temperature limit from -1°C to -6°C. The description below explains how to do it.

How to change the lower temperature limit from -1°C to -6°C

Parameter table

The controller has a lot more configuration, however it is not recommended to change them unless you understand the potential consequences of it. However, it may be useful if you want to verify the settings are correct.

Parameter

Description

Default

SEt

Temperature Setpoint.

dF1

Relay compressor tripping differential. The compressor stops on reaching the Setpoint value (as indicated by the adjustment probe), and restarts at temperature value equal to the Setpoint plus the value of the differential. NOTE: dF1 ≠ 0.

1

HSE

Maximum value that can be assigned to the setpoint.

10

LSE

Minimum value that can be assigned to the setpoint.

-1

0nt

Compressor activation time in the event of inoperable probe.

• If OFt=1 and Ont=0, the compressor is always off.

• If OFt=1 and Ont>0 it operated in duty cycle mode.

0

0Ft

Compressor deactivation time if probe is inoperable.

• If Ont=1 and OFt=0, the compressor is always on.

• If Ont=1 and OFt>0 it operated in duty cycle mode.

0

d0n

Delay time in activating the compressor relay after switch-on of instrument.

1

d0F

Delay after switch-off; the indicated time must elapse between switch-off of the compressor relay and the subsequent switch-on.

1

dbi

Delay between switch-on; the indicated time must elapse between two subsequent switch-on of the compressor.

1

0d0

Delay time in activating the outputs after switch-on of the instrument or after a power outage.

1

Att

Allow you to select if the parameters HAL and LAL will have absolute (Att=0) or relative (Att=1) value.

0

AFd

Alarm differential.

2

HAL

Temperature value (in relative value) which if exceeded in an upward direction triggers the activation of the alarm signal.

30

LAL

Temperature value (in relative value) which if exceeded in a downward direction, triggers the activation of the alarm signal.

-7

PA0

Alarm exclusion time after instrument switch on, after a power outage.

1

tA0

Temperature alarm signal delay time.

5

L0C

LOCK. Setpoint change shutdown. There is still the possibility to enter into parameters programming and modify these, including the status of this parameter to permit keyboard shutdown. n(0) = No; y(1) = Yes.

n

PS1

Password 1. When enabled (PS1 ≠ 0) it constitutes the access key for level 1 parameters.

65

PS2

Password 2. When enabled (PS2 ≠ 0) it constitutes the access key for level 2 parameters.

0

ndt

View with decimal point. n(0) = No; y(1) = Yes (display with decimal).

n

dr0

Select °C or °F for displaying the temperature read by the thermostat probe. (0 = °C, 1 = °F).

NOTE: the switch between °C and °F DO NOT modify setpoint, differential, etc. (for example set=10 °C become 10 °F).

0

ddd

Selection of type of value to be displayed.

0 = Setpoint; 1 = Pb1 probe; 2-3 = Not used.

0

H41

Pb1 present. n(0) = Not present; y(1) = Present.

y

H50

Unknown

0

Last updated